Sentinel+™ Addressable Technology
Automatic reset function for greater stability
Low maintenance requirements due to the absence of moving parts
Sample line up to 20 m
Nearly continuous detection
1 L/min sample flow rate
Excellent zero stability = provides lower and more stable alarm thresholds
Constant-flow monitoring
TOC-750S sampled fixed gas detector, Auto Zero and automatic calibration (Auto Calibrate) It has the following features. The zero port of the 750 Series sampling unit active filtration is equipped with [...], and the system automatically resets periodically; oxygen measurement In that case, he finds himself calibrates automatically.
This feature is for the sensor superior zero stability by ensuring that, compared to the sensor's measurement range, lower alarm levels allows it to be adjusted safely. For example ammonia while the measurement range for detection is 0–1,000 ppm; 25 ppm, 35 ppm, and 500 ppm with alarm levels, as well as exposure monitoring and also Facility Closure under EN 378 These requirements can be fully met.
Power: 24V DC
Weight: 0.85 kg
Temperature Range: -5° to 55°C (23° to 131°F)
Ingress Protection: IP54
Nem %20 ila %90 RH Yoğuşmasız
Installation: Wall Mount
Body Material: ABS
Sensors: Semiconductor, Pellistor, Toxic, PID, Oxygen, Infrared
Communication: IGD Sentinel+™ Protocol, 2-Wire Connection