TOC-30 Analogue Gas Detector
IGD
TOC-30 Analogue Gas Detector
TOC-30 Analog (4-20 mA) gas detectors can be easily integrated into existing or newly planned control systems thanks to their simple design. This feature makes the TOC-30 a preferred solution for industrial safety engineers.
Developed using the latest microprocessor technology and software, the TOC-30 offers a long-term and reliable monitoring solution. It is supplied pre-calibrated and ready for use.
Our TOC-30 series analog gas detector uses the legacy 4-20mA output communication. This allows customers to easily integrate our detectors into third-party controllers or BMS systems. Thus, they obtain a versatile and cost-effective gas detector.
This series of safe area gas detectors is manufactured in robust ABS enclosures that offer various advantages. Sealing is molded as part of the enclosure, which houses the detector and electronics in separate compartments. The detector is protected by a unique labyrinth arrangement that provides both dust and splash protection.
Our analog gas detectors utilize industry-leading, long-lasting sensor technology. This ensures customers have a reliable gas detector that reduces long-term maintenance costs.
Industry Standard 4-20mA Output
Standard 2 Gang Pattress Mount
Dado Mount or Wall Mount
Pre-calibrated
In-Service Calibration Possible
Replaceable Sensor
Weight 200g
Power – 18-28V DC (Loop Powered)
4-20mA Output
+/-2% of Range Accuracy
Temperature = -5 to 55 degrees C
IP54
TUV Tested
Carbon Monoxide (CO) 0-100ppm
Ethylene (C2H4) 0-200ppm
Formaldehyde (CH2O) – 0-5ppm
Carbon Dioxide (CO2) – 0-5000ppm or 0-5% VOL
Ethylene Oxide (ETO) – 0-10ppm
Hydrogen (H2) – 0-1000ppm
Hydrogen Sulphide (H2S) – 0-50ppm
Hydrogen Bromide (HBR) – 0-20ppm
Hydrogen Chloride (HCL) – 0-10ppm
Hydrogen Cyanide (HCN)- 0-10ppm
High range Carbon Monoxide (HCO) – 0-2000ppm
Oxygen (O2) – 0-25% VOL.
Ozone (O3) 0-5ppm
Ammonia (NH3) – 0-100ppm up to 0-5000ppm
Volatile Organic Compounds (VOC) – 0-200ppm and 0-2000ppm
Infrared Flammable (IRF) – 0-100% LEL
Nitric Oxide (NO) – 0-25ppm
Nitrogen Dioxide (NO2) – 0-5ppm
Flammable (FLAM) – 0-100%LEL
Silane (SIH4) – 0-10ppm
Sulphur Dioxide (SO2) – 0-5ppm
Carbon Disulphide (CS2) – 0-100ppm